Why do I get an NI #39 error (Network Interface error) when I try to connect to an i.LON 10 or i.LON 100 using LonMaker Integration Tool? (KB515)

Question Detail
I am using an i.LON 10 or i.LON 100 as a Remote Network Interface (RNI). Why do I get an NI #39 error (Network Interface error) when I try to connect to an i.LON 10 or i.LON 100 using the LonMaker Integration Tool?
 
Solution
NI error #39 is a network interface error. It indicates that the network interface driver failed to open the network interface. For the i.LON 10 or i.LON 100, this error occurs when the LonWorks Interfaces driver configuration on your computer does not match the network interface settings in your i.LON 10 or i.LON 100.

To correct the error, open the LonWorks Interfaces Control Panel program and verify that the port setting, authentication key, hostname, and DNS suffix match the settings in your i.LON 10 or i.LON 100. To open LonWorks Interfaces, click Start, click Control Panel, double-click LonWorks Interfaces, and then click the RNI tab.

Please reference the i.LON 10 or i.LON 100 user guides or online help for instructions in modifying the configuration of an RNI.

When opening your network, make sure you select the correct network interface. For an i.LON 10 or i.LON 100 RNI, the name that you select in the LonMaker tool must match the name that you see on the LonWorks Interfaces RNI tab.

Related Products
  • i.LON 10 Ver 1.0
  • i.LON 10 Ver 2.0
  • i.LON 100 e2 (Ver 1.1)
  • i.LON 100 e3 (Ver 3.0)
  • i.LON 100 Ver 1.0
  • LNS 3.0
  • LNS Turbo Edition (Ver 3.2)
  • LonMaker 3.0
  • LonMaker 3.1
  • LonMaker Turbo (Ver 3.2)
Was this article helpful?
0 out of 0 found this helpful
Have more questions? Submit a request

Comments

Powered by Zendesk