Device replacement causes wrong CP values when loading the application (KB994)

When performing a device replacement in OpenLNS CT with the loading option,  the new device gets the default CP values instead of the LNS database values, even when selecting the LNS database values for the CP source.

You can use this workaround:

1) Define a new device using the new neuron ID and load the application into that device.  

2) Delete the new device.

3) Replace the old device with the new neuron ID