i.LON 700 to SmartServer IoT Re-Imaging Instructions (KB1418)

If you have any issues with the i.LON 700 then you may want to consider re-imaging the i.LON to use the SmartServer IoT software.

The i.LON 700 and SmartServer IoT use the same hardware, only the software is different. You should update the i.LON 700 to SmartServer IoT 2.90 or 3.1. It is always best to update to the latest SmartServer software supported by the hardware.

If you have i.LON 700 software on the SmartServer then most likely this means this is a dual core SmartServer and can only use 3.1 or earlier releases (like 2.9).  If you try to use 3.2+ on a dual core then it can break the SmartServer.

 

The re-imaging instructions are different between the i.LON 700 software and SmartServer IoT software. So first follow the re-imaging instructions below.

 

Re-imaging instructions for the i.LON 700 are different then the SmartServer IoT. Note, even after re-image the i.LON to a SmartServer sometimes when you want to re-image again they will follow these instruction instead of the SmartServer IoT Instructions. 

Re-Image Instructions:

1.     Download and extract the contents of the latest image onto a USB flash drive with atleast 2GB of available space.

It must be formatted with FAT32 file system.

http://iecdocs.diasemi.com/display/PortSSIoT/SmartServer+IoT+Release+Notes

 

2. Unplug any U60s

3. Insert the USB flash drive from step 1 into the i.LON 700 ‘USB1’ port.

4.  Connect to the i.LON 700 console as described below:

 

-   Use a USB cable with a Micro-B plug and connect to the console port on the i.LON 700

-   If you are using a serial terminal emulater, you may have to set the virtual COM port (VCP). To enable this option, open the Windows Device Manager, expand the ‘Universal Serial Controllers category, right-click the USB Serial Converter device added when you plugged in the console connector, and click properties. In the Advanced tab, set the Load VSP option. (image below)

-   Use a USB cable with a Micro-B plug and connect to the console port on the i.LON 700

-   If you are using a serial terminal emulater, you may have to set the virtual COM port (VCP). To enable this option, open the Windows Device Manager, expand the ‘Universal Serial Controllers category, right-click the USB Serial Converter device added when you plugged in the console connector, and click properties. In the Advanced tab, set the Load VSP option. (image below)

mceclip1.png

 

5.     From the terminal/console window:

mceclip2.png

-   Enter the username and password for your iLON 700

-   To re-image the iLON 700, enter the following command at the first prompt:

‘sudo /media/usb0/re-image.sh’

-   Enter your password again at the following prompt: ‘[sudo] password for apollo:’

-   At the next prompt type, ‘sudo reboot’

-   After approx. 15 minutes, the system will reboot and prompt you again to login

 

6.     Login and verify the welcome screen shows the new version that was installed

mceclip3.png

 